The module produces 1 byte for every 8 inputs. Similarly, the module
consumes 1 byte for every 8 outputs. When an expansion module is
connected, an additional byte will be returned indicating the health of
the expansion module.
Remember, though, when configuring your CompactBlock I/O
application, these values are entered as bytes received (R
x
) and bytes
transmitted (T
x
) by the scanner.
For example, a Base input module produces 2 bytes and consumes 0
bytes. In such a case, the scanner connected to the Base Input
module will receive (R
x
) 2 bytes and transmit (T
x
) 0 bytes.
Word/Bit Definitions
The following table lists the combination of input and output
modules and the input and output bytes produced and consumed.
IMPORTANT
When installing an expansion module, refer to the
table below to see how many bytes are produced
and consumed by the modules.
Digital Expander
Base
Expansion
I/O Points
Produced
(input bytes)
Consumed
(output bytes)
16 input
16 in
2
0
16 output
16 out
0
2
8 in / 8 out
8 in / 8 out
1
1
4 in
4 in
1
0
4 in / 4 out
4 in / 4 out
1
1
8 out
8 out
0
1
16 input
16 input
32 input
5
0
16 input
16 output
16 in / 16 out
3
2
16 output
16 input
16 in / 16 out
3
2