Rockwell Automation 1791D-XXXX CompactBlock I/O for DeviceNet Modules Series D I.I. User Manual

Page 16

Advertising
background image

16 CompactBlock I/O for DeviceNet Modules Series D

Publication

1791D-IN003A-EN-P - June 2003

The module produces 1 byte for every 8 inputs. Similarly, the module
consumes 1 byte for every 8 outputs. When an expansion module is
connected, an additional byte will be returned indicating the health of

the expansion module.

Remember, though, when configuring your CompactBlock I/O
application, these values are entered as bytes received (R

x

) and bytes

transmitted (T

x

) by the scanner.

For example, a Base input module produces 2 bytes and consumes 0
bytes. In such a case, the scanner connected to the Base Input
module will receive (R

x

) 2 bytes and transmit (T

x

) 0 bytes.

Word/Bit Definitions

The following table lists the combination of input and output
modules and the input and output bytes produced and consumed.

IMPORTANT

When installing an expansion module, refer to the
table below to see how many bytes are produced
and consumed by the modules.

Digital Expander

Base

Expansion

I/O Points

Produced

(input bytes)

Consumed
(output bytes)

16 input

16 in

2

0

16 output

16 out

0

2

8 in / 8 out

8 in / 8 out

1

1

4 in

4 in

1

0

4 in / 4 out

4 in / 4 out

1

1

8 out

8 out

0

1

16 input

16 input

32 input

5

0

16 input

16 output

16 in / 16 out

3

2

16 output

16 input

16 in / 16 out

3

2