North american hazardous location approval – Rockwell Automation 1791D-XXXX CompactBlock I/O for DeviceNet Modules Series D I.I. User Manual

Page 24

Advertising
background image

24 CompactBlock I/O for DeviceNet Modules Series D

Publication

1791D-IN003A-EN-P - June 2003

North American Hazardous Location Approval

The following information applies when
operating this equipment in hazardous locations:

Informations sur l’utilisation de cet équipement en
environnements dangereux :

Products marked “CL I, DIV 2, GP A, B, C, D” are suitable
for use in Class I Division 2 Groups A, B, C, D,
Hazardous Locations and nonhazardous locations only.
Each product is supplied with markings on the rating
nameplate indicating the hazardous location
temperature code. When combining products within a
system, the most adverse temperature code (lowest “T”
number) may be used to help determine the overall
temperature code of the system. Combinations of
equipment in your system are subject to investigation
by the local Authority Having Jurisdiction at the time of
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu’à une utilisation en environnements de Classe
I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque
d’identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être
utilisé pour déterminer le code de température global du
système. Les combinaisons d’équipements dans le système
sont sujettes à inspection par les autorités locales qualifiées
au moment de l’installation.

!

WARNING

EXPLOSION HAZARD

• Do not disconnect

equipment unless
power has been
removed or the area is
known to be
nonhazardous.

• Do not disconnect

connections to this
equipment unless
power has been
removed or the area is
known to be
nonhazardous. Secure
any external
connections that mate
to this equipment by
using screws, sliding
latches, threaded
connectors, or other
means provided with
this product.

• Substitution of

components may
impair suitability for
Class I, Division 2.

• If this product contains

batteries, they must
only be changed in an
area known to be
nonhazardous.

AVERTISSEMENT

!

RISQUE D’EXPLOSION

• Couper le courant ou

s’assurer que
l’environnement est
classé non dangereux
avant de débrancher
l'équipement.

• Couper le courant ou

s'assurer que
l’environnement est
classé non dangereux
avant de débrancher
les connecteurs. Fixer
tous les connecteurs
externes reliés à cet
équipement à l'aide de
vis, loquets
coulissants,
connecteurs filetés ou
autres moyens fournis
avec ce produit.

• La substitution de

composants peut
rendre cet équipement
inadapté à une
utilisation en
environnement de
Classe I, Division 2.

• S’assurer que

l’environnement est
classé non dangereux
avant de changer les
piles.

Advertising