Troubleshoot with the Indicators

The 1791D I/O module has the following indicators:

• Mod/Net status indicator - base only
• Logic status indicator - base only
• I/O status indicators - base and expansion

Mod/Net Status Indicator

Indication:

Status:

Off

No power or auto bauding

Flashing Green/Off On line but not connected

Solid Green

On line, link OK, connected

Flashing Red

Recoverable fault - (expansion module fault or module configuration
error)

I/O connection fault - one or more I/O connections in the timed-out state

Mod/Net Status Indicator (continued)

Indication:

Status:

Solid Red

Unrecoverable fault

Communication failure - duplicate node address present or incorrect
baud rate

Green to Red to Off At powerup only - LED test

Logic Status Indicator

Indication:

Status:

Off

Logic is disabled

Solid Green

Logic is enabled

Flashing Green

Local forces are applied and local logic is enabled