12 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug

Publication

1792D-IN055A-EN-P - October 2004

The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at
http://www.ab.com/networks for producer/consumer technology
information and updates.

Byte

Bit

Description

Produces 0

00-07

Input Status bits: When the bit is set (1), the input is on.

Bit 00 = input 0, bit 01 = input 1, bit 02 = input 2, and so on to bit
07 = input 7.

Produces 1

00-03

04-07

Input short circuit fault: ISC-A = a short circuit for connector A
Input short circuit fault: ISC-B = a short circuit for connector B
Input short circuit fault: ISC-C = a short circuit for connector C
Input short circuit fault: ISC-D = a short circuit for connector D
Input off wire fault: OW-A = an off-wire fault for connector A
Input off wire fault: OW-B = an off-wire fault for connector B
Input off wire fault: OW-C = an off-wire fault for connector C
Input off wire fault: OW-D = an off-wire fault for connector D

Produces 2

00-07

Output no load or overload fault (OFLT): - When the bit is set (1)
an output fault has occurred. OFLT0 = output 0, OFLT1 = output
1, OFLT2 = output 2, and so on to OFLT7 = output 7.

Produces 3

00-05
06

07

RSVD = Reserved
Output Power Fault (OPWR): When the bit is set (1) auxiliary
power is not present.
RSVD = Reserved

Consumes 0

00-07

Output bits: When the bit is set (1), the output will be turned on.
Bit O0 = output O0, bit 01 = output O1, bit 02 = output O2, and
so on to bit O7 = output O7.