Rockwell Automation 1792D-8BT8PE ArmorBlock MaXum 8 In/8 Out Module with Ground Lug User Manual
Page 8
![background image](/manuals/579205/8/background.png)
8 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug
Publication
1792D-IN055A-EN-P - October 2004
Refer to publication 889-5.0 for Rockwell Automation cables and cord
sets offerings.
WARNING
Use supply wires suitable for 30°C above
surrounding ambient.
IMPORTANT
If the devices (sensors) connected to the input
connections require Class 2 power to operate, the
DeviceNet connections of this equipment must be
powered by a Class 2 source.
ATTENTION
• Make sure all connections and caps are securely
tightened to properly seal the connections against
leaks and maintain IP67 requirements.
• For maximum noise immunity, input and output
cable return wires must be properly terminated.
When inputs and outputs are connected in
loopback, return wires should be connected
together.
• I/O cable length should be less than 30 meters.