North american hazardous location approval – Rockwell Automation 1792D-8BT8PE ArmorBlock MaXum 8 In/8 Out Module with Ground Lug User Manual
Page 19
 
ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 19
Publication
1792D-IN055A-EN-P - October 2004
North American Hazardous Location Approval
ArmorBlock, ArmorBlock MaXum, RSNetWorx for DeviceNet, DeviceNetManager, and KwikLink are 
trademarks of Rockwell Automation.
DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA).
The following information applies when operating 
this equipment in hazardous locations:
Informations sur l'utilisation de cet équipement en 
environnements dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable 
for use in Class I Division 2 Groups A, B, C, D, Hazardous 
Locations and nonhazardous locations only. Each product 
is supplied with markings on the rating nameplate 
indicating the hazardous location temperature code. 
When combining products within a system, the most 
adverse temperature code (lowest "T" number) may be 
used to help determine the overall temperature code of 
the system. Combinations of equipment in your system 
are subject to investigation by the local Authority Having 
Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu'à une utilisation en environnements de 
Classe I Division 2 Groupes A, B, C, D dangereux et non 
dangereux. Chaque produit est livré avec des marquages sur 
sa plaque d'identification qui indiquent le code de 
température pour les environnements dangereux. Lorsque 
plusieurs produits sont combinés dans un système, le code 
de température le plus défavorable (code de température le 
plus faible) peut être utilisé pour déterminer le code de 
température global du système. Les combinaisons 
d'équipements dans le système sont sujettes à inspection 
par les autorités locales qualifiées au moment de 
l'installation.
WARNING
• Do not disconnect equipment
unless power has been 
removed or the area is known 
to be nonhazardous. 
• Do not disconnect
connections to this 
equipment unless power has 
been removed or the area is 
known to be nonhazardous. 
Secure any external 
connections that mate to this 
equipment by using screws, 
sliding latches, threaded 
connectors, or other means 
provided with this product.
• Substitution of components
may impair suitability for 
Class I, Division 2.
• If this product contains
batteries, they must only be 
changed in an area known to 
be nonhazardous.
AVERTISSEMENT
• Couper le courant ou
s'assurer que 
l'environnement est classé 
non dangereux avant de 
débrancher l'équipement.
• Couper le courant ou
s'assurer que 
l'environnement est classé 
non dangereux avant de 
débrancher les 
connecteurs. Fixer tous les 
connecteurs externes 
reliés à cet équipement à 
l'aide de vis, loquets 
coulissants, connecteurs 
filetés ou autres moyens 
fournis avec ce produit.
• La substitution de
composants peut rendre 
cet équipement inadapté à 
une utilisation en 
environnement de Classe I, 
Division 2.
• S'assurer que
l'environnement est classé 
non dangereux avant de 
changer les piles.