Install the module – Rockwell Automation 1792D-8BT8PE ArmorBlock MaXum 8 In/8 Out Module with Ground Lug User Manual

Page 5

Advertising
background image

ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 5

Publication

1792D-IN055A-EN-P - October 2004

To reset the node address, use a small blade screwdriver to rotate the
switches. Line up the small black dot on the switch with the number
setting you wish to use.

The rotary switches are read at module power up only. Settings from
64 through 99 cause the module to use the last valid node address
stored internally. For example, the last setting was 40. If a change is
made to 68, and then you power up, the address will default to 40.

Refer to the following illustration of the node address.

The module is equipped with AutoBaud detect. AutoBaud lets the
module read the settings already in use on your DeviceNet network
and automatically adjusts to follow those settings.

Install the Module

This module mounts to the following cable bases:

• 1792D-CBFM for KwikLink™ flat media installation

• 1792D-CB12 for 12mm drop cable installation

• 1792D-CB18P for round media DeviceNet and output power

• other optional cable base assembly.

IMPORTANT

The cable base should already be installed. For
more information about the cable base, see
publication 1792D-IN036 (CB18P) or 1792D-IN009
(CBFM, CB12).

NODE ADDRESS

(00-63 PGM)

LSD

MSD

0 1

2
3

4

5

8

9

7

6

0 1

2
3

4

5

8

9

7

6

Bottom View of Module

41462

Node Address
is set at 62;
see small
black dots.