I/o memory mapping, Input data file – Rockwell Automation 1769-IF4XOF2 Compact Combination Analog Module User Manual
Page 14
 
14 Compact™ Combination Analog I/O Module
Publication 1769-IN057A-EN-P - July 2001
I/O Memory Mapping
Input Data File
The input data file provides access to input data for use in the control program, 
over-range indication for the input and output channels, and output data feedback 
as described below.
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
SGN
Analog Input Data Channel 0
0
0
0
0
0
0
0
1
SGN
Analog Input Data Channel 1
0
0
0
0
0
0
0
2
SGN
Analog Input Data Channel 2
0
0
0
0
0
0
0
3
SGN
Analog Input Data Channel 3
0
0
0
0
0
0
0
4
Not Used
(1)
(1)
All unused bits are set to 0 by the module.
I3
I2
I1
I0
5
Not
Used
H0
Not
Used
H1
Not Used
E1
E0
O1
O0
6
SGN
Output Data Echo/Loopback for Output Channel 0
0
0
0
0
0
0
0
7
SGN
Output Data Echo/Loopback for Output Channel 1
0
0
0
0
0
0
0
IMPORTANT
Input words 6 and 7 contain the Output Data Echo/Loopback 
information for output channels 0 and 1 respectively. Bits 0 
through 6 and Bit 15 of words 6 and 7 should always be set to 
zero in your control program. If they are not set to 0, the invalid 
data flag (Ex) will be set for that channel by the module. 
However the channel will continue to operate with the 
previously converted value.