I/O Memory Mapping

Input Data File

The input data file provides access to input data for use in the control program,
over-range indication for the input and output channels, and output data feedback
as described below.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

SGN

Analog Input Data Channel 0

0

0

0

0

0

0

0

1

SGN

Analog Input Data Channel 1

0

0

0

0

0

0

0

2

SGN

Analog Input Data Channel 2

0

0

0

0

0

0

0

3

SGN

Analog Input Data Channel 3

0

0

0

0

0

0

0

4

Not Used

(1)

(1)

All unused bits are set to 0 by the module.

I3

I2

I1

I0

5

Not

Used

H0

Not

Used

H1

Not Used

(1)

E1

E0

O1

O0

6

SGN

Output Data Echo/Loopback for Output Channel 0

0

0

0

0

0

0

0

7

SGN

Output Data Echo/Loopback for Output Channel 1

0

0

0

0

0

0

0

IMPORTANT

Input words 6 and 7 contain the Output Data Echo/Loopback
information for output channels 0 and 1 respectively. Bits 0
through 6 and Bit 15 of words 6 and 7 should always be set to
zero in your control program. If they are not set to 0, the invalid
data flag (Ex) will be set for that channel by the module.
However the channel will continue to operate with the
previously converted value.