16 Compact™ Combination Analog I/O Module

Publication 1769-IN057A-EN-P - July 2001

Output Data File

The output data file applies only to output data from the module as shown in the
table below.

Wor

d

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

SGN

Analog Output Data Channel 0

0

0

0

0

0

0

0

1

SGN

Analog Output Data Channel 1

0

0

0

0

0

0

0

IMPORTANT

Bits 0 through 6 and Bit 15 of output data words 0 and 1 should
always be set to zero in your control program. If they are not set
to 0, the invalid data flag (Ex) will be set for that channel.
However the channel will continue to operate with the
previously converted value. If a MVM (Move with Mask)
instruction is used with a mask of 7F80 (hexidecimal) to move
data to the output words, writing to bits 0 through 6 and bit 15
can be avoided.