Wiring differential inputs – Rockwell Automation 1769-IF4XOF2 Compact Combination Analog Module User Manual

Page 9

Advertising
background image

Compact™ Combination Analog I/O Module 9

Publication 1769-IN057A-EN-P - July 2001

Voltage outputs (Vout 0+ and Vout 1+) of the 1769-IF4XOF2 module are
referenced to ANLG COM. Load resistance for a voltage output channel must
be equal to or greater than 1K

.

Current outputs (Iout 0+ and Iout 1+) of the 1769-IF4XOF2 module source
current that returns to ANLG COM. Load resistance for a current output
channel must remain between 0 and 300

.

Voltages on Vin+, V/Iin-, and Iin+ of the 1769-IF4XOF2 module must be
within 0 to +10V dc of analog common.

Wiring Differential Inputs

ATTENTION

!

Be careful when stripping wires. Wire fragments that fall into
a module could cause damage at power up. Once wiring is
complete, ensure the module is free of all metal fragments.

+

V in 1+

V in 3+

V in 0+

V/I in 0-

I in 1+

I in 3+

V/I in 1 -

I in 0+

I in 2+

V in 2 +

V/I in 3 -

V/I in 2-

ANLG Com

ANLG Com

V out 1+

I out 1+

V out 0+

I out 0+

earth ground the

shield locally at the

module

differential voltage

transmitter

Belden 8761 cable (or equivalent)

Advertising