Rockwell Automation 1769-IF4XOF2 Compact Combination Analog Module User Manual

Page 22

Advertising
background image

22 Compact™ Combination Analog I/O Module

Publication 1769-IN057A-EN-P - July 2001

Output Ripple

(3)

range 0 to 50 kHz
(referred to output range)

±0.05%

Non-linearity (in percent full scale)

±0.4%

Repeatability

(4)

(in percent full scale)

±0.05%

Output Impedance

10

(nominal)

Open and Short-Circuit Protection

Yes

Maximum Short-Circuit

Current: 40 mA

Maximum Open Circuit

Voltage: 15V

Output Response at System Power Up
and Power Down

+2.0V dc to -1.0V dc spike for less than 6 ms

Output Group to Bus Isolation

500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)

Channel Diagnostics

Over-range by bit reporting

(1)

The over-range flag will come on when the normal operating range is exceeded. The module will continue to convert the
analog output up to the maximum full scale range. The flag automatically resets when within the normal operating range.

(2)

Includes offset, gain, drift, non-linearity and repeatability error terms.

(3)

Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.

(4)

Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it
consecutively, under the same conditions and in the same direction.

Output Specification

1769-IF4XOF2

Advertising