18 Compact™ Combination Analog I/O Module
Publication 1769-IN057A-EN-P - July 2001
Hold Last State (0) – When reset, this bit directs the module to hold the 
analog output at the last converted value when the module transitions to 
Program Mode. This is the default condition.
User-Defined Safe State (1) – When this bit is set and the module transitions 
to Program mode, the module converts the user-specified integer value from 
the Channel x Program Value Word (3 or 5) to the appropriate analog output 
for the configured range as wired.
•
FMx = These bits provide Fault Mode selection for analog output channels 0 
and 1.
Hold Last State (0) – When reset, this bit directs the module to hold the 
analog output at the last converted value when the module transitions to 
Fault Mode. This is the default condition.
User-Defined Safe State (1) – When this bit is set and the module transitions 
to Fault mode, the module converts the user-specified integer value from the 
Channel x Fault Value Word (2 or 4) to the appropriate analog output for the 
configured range as wired.
•
PFEx = The Program to Fault Enable bit determines which data value, 
Program (PFEx = 0) or Fault (PFEx = 1), is applied to the output if the 
module undergoes a fault condition while in the Program Mode, resulting in 
a change to Fault Mode.
•
Channel x Program (Idle) Value
Words 3 and 5 allow you to enter the integer values that output Channel 0 
(Word 3) and output Channel 1 (Word 5) should assume when the system 
transitions to the Program mode. The value must be in increments of 128 (0, 
128, 256, etc.) for proper operation. If the value entered is outside the 
acceptable increment or range, the module generates a configuration error 
for that channel. The module default is zero.
••••
Channel x Fault Value
Words 2 and 4 allow you to enter the integer values that output Channel 0 
(Word 2) and output Channel 1 (Word 4) should assume when the system 
transitions to the Fault mode. The value must be in increments of 128 (0, 
128, 256, etc.) for proper operation. If the value entered is outside the 
acceptable increment or range, the module generates a configuration error 
for that channel. The module default is zero.
IMPORTANT
PMx, FMx, PFEx, Channel x Program (Idle) Value, and Channel x 
Fault Value functions are not supported by all controllers. Refer 
to your controller’s user manual for details.