Specifications, General specifications – Rockwell Automation 1769-IF4XOF2 Compact Combination Analog Module User Manual

Page 19

Advertising
background image

Compact™ Combination Analog I/O Module 19

Publication 1769-IN057A-EN-P - July 2001

Specifications

General Specifications

Specification

1769-IF4XOF2

Dimensions

118 mm (height) x 87 mm (depth) x 35 mm (width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width)
height including mounting tabs is 5.43 in.

Approximate Shipping Weight
(with carton)

290g (0.64 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +60°C (32°F to +140°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G (when a relay module is used in the system)

Shock

Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Relay Operation: 7.5G panel mounted
(5G DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)

Bus Current Draw (max.)

120 mA at 5V dc
160 mA at 24V dc

Heat Dissipation

3.03 Total Watts (The Watts per point, plus the minimum Watts,
with all points energized.)

System Power Supply Distance Rating

8 (The module may not be more than 8 modules away from the
system power supply.)

Recommended Input/Output Cable

Belden™ 8761 (shielded)

Max. Input/Output Cable Length

200m (656 feet) Exceeding cable length reduces accuracy. For
more information, see the Compact Combination Analog Module
User Manual, publication number 1769-UM008A-EN-P.

Module OK LED

On: module has power, has passed internal diagnostics, and is
communicating over the bus.
Off: Any of the above is not true.

Field Calibration

None required

Vendor I.D. Code

1

Product Type Code

10

Product Code

33

Agency Certification

C-UL certified (under CSA C22.2 No. 142)

UL 508 listed

CE and C-Tick compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
C-UL under CSA C22.2 No. 213)

Radiated and Conducted Emissions

EN50081-2 Class A

Advertising