Rockwell Automation 1771-P7 AC (120/220V) 16A Power Supply Installation Instructions User Manual

Page 11

Advertising
background image

I

0

I

POWER

0

115V

12625ĆI

AC (120/220V) 16A Power Supply

11

Publication 1771ĆIN056B EN-P - December 2001

The power supply operates on nominal 120V ac or 220V ac
input source.

1. Make sure the power switch is set to 0 (off).

2. Use a 1/8” slotted screwdriver to set the input-voltage

selector switch.

!

WARNING

Do not set the input voltage selector switch with
power applied. This could cause an electrical arc
which could cause an explosion in hazardous
location installations. Be sure power is removed
or the area is nonhazardous before proceeding.

!

ATTENTION

To avoid damaging the power supply, do not
place the screwdriver blade more than 3/8”
into the switch slot.

For an input voltage of

Set the voltage selector switch to

97 to 132V ac

115 position

115V

195 to 264V ac

230V

230 position

3. Connect the ac power line to the terminal strip on the

power supply.

!

WARNING

If you connect or disconnect the ac power line to
the terminal strip with power applied an electrical
arc can occur. This could cause an explosion in
hazardous location installations. Be sure power is
removed or the area is nonhazardous before
proceeding.

!

ATTENTION

You must connect a 14 AWG wire from the GND
terminal to the ground bus to provide an adequate
safety ground.

Connect ac Power Source

to the Power Supply

Advertising