AC (120/220V) 16A Power Supply

6

Publication1771ĆIN056B EN-P - December 2001

Attaching to a PanelĆmounted I/O Chassis

1. Attach the mounting screws to the side of the I/O chassis:

!

ATTENTION

Use the mounting screws provided with the
1771-P7. Longer screws may intrude into the
I/O chassis and interfere with module
insertion.

large screw

lockwasher

shoulder washer

Tighten this screw until snug,

plus 1/4 turn (about 29

pound-inches).

two small screws

and lockwashers

Loosely attach these screws.

leftĆside of I/O chassis

13446

2. Connect the power cable (ordered separately) to the D-shell

connector on the I/O chassis and tighten the connector screws.

!

WARNING

If you connect or disconnect the power supply
cable with power applied an electrical arc can
occur. This could cause an explosion in hazardous
location installations. Be sure power is removed
or the area is nonhazardous before proceeding.

DĆshell connector

1771ĆCP1 cable

connector screws

leftĆside of I/O chassis

13447

Tighten connectorscrews

until snug, plus 1/4 turn).