Wire analog outputs, Label the terminals, Remove the finger-safe terminal block – Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual

Page 15: Wire analog outputs label the terminals

Advertising
background image

Compact Combination Fast Analog I/O Module 15

Publication 1769-IN081A-EN-P - February 2007

Wire Analog Outputs

Label the Terminals

A removable, write-on label is provided with the module. Remove the label from
the door, mark the identification of each terminal with permanent ink, and slide the
label back into the door. Your markings (ID tag) will be visible when the module
door is closed.

Remove the Finger-safe Terminal Block

When wiring field devices to the module, it is not necessary to remove the terminal
block. If you remove the terminal block, use the write-on label on the side of the
terminal block to identify the module slot location and type.

ATTENTION

Analog outputs may fluctuate for less than a second when power is applied
or removed. This characteristic is common to most analog outputs. While
the majority of loads will not recognize this short signal, take preventive
measures to ensure that connected equipment is not affected. Failure to
take these preventative measures may result in unexpected load reactions.

V in 0+

V/I in 0 -

I in 0+

V in 1+

V/I in 1-

I in 1+

V in 2+

V/I in 2-

I in 2+

ANLG Com

ANLG Com

V in 3+

I out 0+

V out 0+

I out 1 +

V out 1+

V/I in 3-

I in 3+

Voltage Load

Current Load

Earth Ground

Earth Ground

1769-IF4FXOF2F Terminal Block

SLOT # _____

MODULE TYPE ______