Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual
Page 21

Compact Combination Fast Analog I/O Module 21
Publication 1769-IN081A-EN-P - February 2007
•
Process Alarm High Data Value Channel x = Provides the ability to configure
the Input Process Alarm High Value.
•
Process Alarm Low Data Value Channel x = Provides the ability to configure
the Input Process Alarm Low Value.
•
Alarm Dead Band Value Channel x = Provides the ability to configure the
Input Process Dead Band Value.
•
Reserved = Bits not used, must be set to 0.
•
EHI = Enable Output Channel Interrupt on High Clamp Alarm.
•
ELI = Enable Output Channel Interrupt on Low Clamp Alarm.
•
LC = Latch Low/High Clamp and Under/Over Range Alarm.
•
ER = Enable Ramping.
•
FM = Enable Fault Alternate Output State mode.
•
PM = Enable Program/Idle Alternate Output State mode.
•
PFE = Enable Program/Idle to Fault Alternate Output State mode.
•
Outpt Fm ChIx = Output Data Format Select.
•
Outpt Tp/Rnge Sel ChIx = Output Type/Range Select.
•
Ramp Rate Channel x = Provides the ability to configure the Ramp Rate.
Define
To
Select
Make these bit settings
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Input Filter
Selection /
-3 dB
Frequency
60 Hz
0
0
0
0
50 Hz
0
0
0
1
5 Hz
0
0
1
0
10 Hz
0
0
1
1
100 Hz
0
1
0
0
250 Hz
0
1
0
1
500 Hz
0
1
1
0
1000 Hz
0
1
1
1
No
Filter
1
0
0
0