Compact Combination Fast Analog I/O Module 19

Publication 1769-IN081A-EN-P - February 2007

Configuration Data File

The manipulation of bits from this file is normally done with programming software
(for example, RSLogix 500 software or RSNetWorx for DeviceNet software) during
initial configuration of the system. In that case, graphical screens provided by the
programming software simplify configuration.

Some systems, like the 1769-ADN DeviceNet adapter system, also allow the bits to
be altered as part of the control program using communication rungs. In that case,
it is necessary to understand the bit arrangement.

Word/Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word 0

0

Real Time Sample Value

Word 1

ETS

Reserved

Word 2

EC

Reserved

EA

AL

EI

Reserved

Input Filter Sel ChI0

Word 3

Reserved

Input Dta Fm
ChI0

Reserved

Inpt Tp/Rnge Sel ChI0

Word 4

SGN

Process Alarm High Data Value Channel 0

0

Word 5

SGN

Process Alarm Low Data Value Channel 0

0

Word 6

SGN

Alarm Dead Band Value Channel 0

0

Word 7

Reserved

Word 8

EC

Reserved

EA

AL

EI

Reserved

Input Filter Sel ChI1

Word 9

Reserved

Input Dta Fm
ChI1

Reserved

Inpt Tp/Rnge Sel ChI1

Word 10

SGN

Process Alarm High Data Value Channel 1

0

Word 11

SGN

Process Alarm Low Data Value Channel 1

0

Word 12

SGN

Alarm Dead Band Value Channel 1

0

Word 13

Reserved

Word 14

EC

Reserved

EA

AL

EI

Reserved

Input Filter Sel ChI2

Word 15

Reserved

Input Dta Fm
ChI2

Reserved

Inpt Tp/Rnge Sel ChI2

Word 16

SGN

Process Alarm High Data Value Channel 2

0

Word 17

SGN

Process Alarm Low Data Value Channel 2

0

Word 18

SGN

Alarm Dead Band Value Channel 2

0

Word 19

Reserved

Word 20

EC

Reserved

EA

AL

EI

Reserved

Input Filter Sel ChI3

Word 21

Reserved

Input Dta Fm
ChI3

Reserved

Inpt Tp/Rnge Sel ChI3