Compact Combination Fast Analog I/O Module 17

Publication 1769-IN081A-EN-P - February 2007

Wire Size and Terminal Screw Torque

Each terminal accepts two wires with the following restrictions:.

Configure the 1769-IF4FXOF2F Module

The following I/O memory mapping lets you configure the 1769-IF4FXOF2F
module.

Output Data File

For each module, slot x, words 0 and 1 in the output data file contain the control
program’s directed state of the module’s analog output channels. Word 2 contains
the cancel input channel alarm control bits. Word 3 contains the cancel output
channel clamp control bits.

The bits are defined as follows:

SGN = Sign bit in 2’s complement format.

CHIx = Cancel High Process Alarm Latch for Input x: Allows each input
high-process-alarm latch to be individually cancelled. NOTE: Cancel = 1.

CLIx = Cancel Low Process Alarm Latch for Input x: Allows each input
low-process-alarm latch to be individually cancelled. NOTE: Cancel = 1.

CHOx = Cancel High Clamp Alarm Latch for Output x: Allows each output
high-clamp-alarm latch to be individually cancelled. NOTE: Cancel = 1.

CLOx = Cancel Low Clamp Alarm Latch for Output x: Allows each output
low-clamp-alarm-latch to be individually cancelled. NOTE: Cancel = 1.

Wire Type

Wire Size

Terminal Screw
Torque

Retaining Screw
Torque

Solid

Cu-90°C (194°F)

#14…#22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Stranded

Cu-90°C (194°F)

#16…#22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Word/Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word 0

SGN

Analog Output Data Channel 0

0

0

Word 1

SGN

Analog Output Data Channel 1

0

0

Word 2

0

0

0

0

0

0

0

0

CL
I3

CH
I3

CL
I2

CH
I2

CL
I1

CH
I1

CL
I0

CH
I0

Word 3

0

0

0

0

0

0

0

0

0

0

0

0

CL
O1

CH
O1

CL
O0

CH
O0

Advertising