Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual

Page 24

Advertising
background image

24 Compact Combination Fast Analog I/O Module

Publication 1769-IN081A-EN-P - February 2007

Certifications

Certification

Value

Agency Certification

C-UL certified (under CSA C22.2 No. 142)

UL 508 listed

CE compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
C-UL under CSA C22.2 No. 213)

Radiated and Conducted Emissions

EN50081-2 Class A

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity (IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (IEC1000-4-3)

10 V/m, 80…1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier

Fast Transient Burst (IEC1000-4-4)

2 kV, 5 kHz

Surge Immunity (IEC1000-4-5)

1 kV galvanic gun

Conducted Immunity
(IEC1000-4-6)

10V dc, 0.15…80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is 30 MHz…1000
MHz.

Output Specifications

Attribute

Value

Analog Normal Operating Ranges

(1)

(1)

The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will
continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the
normal operating range unless configured to latch.

0…20 mA, 4…20 mA, +/-10V dc, 0…10V dc, 0…5 V dc, 1…5V dc

Full Scale Analog Ranges

(1)

0…21 mA, 3.2…21 mA, +/-10.5V dc, -0.5…10.5V dc, -0.5… 5.25V
dc, 0.5… 5.25V dc

Number of Outputs

Two single-ended

Digital Resolution Across Full Range

13 bits unipolar, 13 bits plus sign bipolar

Conversion Rate (all channels) max.

1 ms

Step Response to 63%

(2)

(2)

Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until
the device is at 63% of full range.

2.0 ms

Resistive Load

Current: 0…500

(includes wire resistance)

Voltage: 1 K

or greater

Max. Inductive Load

0.1 mH (current loads), 1.0 uF (voltage loads)

Field Calibration

None required

Overall Accuracy

(3)

(3)

Includes offset, gain, drift, non-linearity and repeatability error terms.

0.2% full scale at 25 °C