20 Compact Combination Fast Analog I/O Module

Publication 1769-IN081A-EN-P - February 2007

The bits are defined as follows:

SGN = Sign bit in 2’s complement format.

Real Time Sample Value = Provides the ability to configure the Real Time
Sample Rate.

ETS = Enable Time Stamping.

EC = Enable Channel.

EA = Enable Alarm.

AL = Alarm Latch.

EI = Enable Input Process Alarm Interrupt.

Input Filter Sel ChIx = Input Channel Filter Setting.

Inpt Dta Fm ChIx = Input Data Format Select.

Inpt Tp/Rnge Sel ChIx = Input Type/Range Select.

Word 22

SGN

Process Alarm High Data Value Channel 3

0

Word 23

SGN

Process Alarm Low Data Value Channel 3

0

Word 24

SGN

Alarm Dead Band Value Channel 3

0

Word 25

Reserved

Word 26

EC

Reserved

EHI

ELI

LC

ER

FM

PM

0

PFE

Word 27

Reserved

Outpt Fm ChI0

Reserved

Outpt Tp/Rnge Sel
ChI0

Word 28

SGN

Fault Value Channel 0

0

0

Word 29

SGN

Program (Idle) Value Channel 0

0

0

Word 30

SGN

Clamp High Data Value Channel 0

0

0

Word 31

SGN

Clamp Low Data Value Channel 0

0

0

Word 32

SGN

Ramp Rate Channel 0

0

0

Word 33

Reserved

Word 34

EC

Reserved

EHI

ELI

LC

ER

FM

PM

0

PFE

Word 35

Reserved

Outpt Fm ChI1

Reserved

Outpt Tp/Rnge Sel
ChI1

Word 36

SGN

Fault Value Channel 1

0

0

Word 37

SGN

Program (Idle) Value Channel 1

0

0

Word 38

SGN

Clamp High Data Value Channel 1

0

0

Word 39

SGN

Clamp Low Data Value Channel 1

0

0

Word 40

SGN

Ramp Rate Channel 1

0

0

Word 41

Reserved

Advertising