Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual
Page 15

MicroLogix 1200 Thermocouple/mV Input Module 15
Publication 1762-IN013B-EN-P - June 2013
To Select
Make these bit settings
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Filter F
requency
10 Hz
No
t U
sed
(1
)
(1)
An attempt to write any non-valid (spare) bit configuration into any selection field results in a module configuration error.
1
1
0
60 Hz
0
0
0
50 Hz
0
0
1
250Hz
0
1
1
500 Hz
1
0
0
1 kHz
1
0
1
Op
en Circuit
Upscale
0
0
Downscale
0
1
Hold Last State
1
0
Zero
1
1
Te
mperatu
re
Un
its
Degrees C
0
Degrees F
1
Input T
ype
Thermocouple J
0
0
0
0
Thermocouple K
0
0
0
1
Thermocouple T
0
0
1
0
Thermocouple E
0
0
1
1
Thermocouple R
0
1
0
0
Thermocouple S
0
1
0
1
Thermocouple B
0
1
1
0
Thermocouple N
0
1
1
1
Thermocouple C
1
0
0
0
-50…50 mV
1
0
0
1
-100…100 mV
1
0
1
0
Data
Format
Raw/Proportional
0
0
0
Engineering Units
0
0
1
Engineering UnitsX10
1
0
0
Scaled-for-PID
0
1
0
Percent Range
0
1
1
En
able
Channel
Disable
0
Enable
1
TIP
Program defaults are indicated by zero (0) values. For example, type J
thermocouple is the default (no user intervention) thermocouple type.