MicroLogix 1200 Thermocouple/mV Input Module 9

Publication 1762-IN013B-EN-P - June 2013

• Ground the shield drain wire at one end only. The typical location is the same point as

the sensor ground reference.

– For grounded thermocouples or millivolt sensors, this is at the sensor end.
– For insulated/ungrounded thermocouples, this is at the module end. Contact your

sensor manufacturer for additional details.

• If it is necessary to connect the shield drain at the module end, connect it to earth

ground using a panel or DIN rail mounting screw.

• Routing the field wiring in a grounded conduit can further reduce electrical noise.

Terminal Block Layout

Labeling the Terminals

A write-on label is provided with the module. Mark the identification of each terminal with
permanent ink, and slide the label back into the door.

IN1 -

IN1 +

IN 0 -

IN 0 +

IN2 -

IN2 +

CJC

CJC

IN3 -

IN3 +