Terminal block layout labeling the terminals – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 9

Advertising
background image

MicroLogix 1200 Thermocouple/mV Input Module 9

Publication 1762-IN013B-EN-P - June 2013

• Ground the shield drain wire at one end only. The typical location is the same point as

the sensor ground reference.

For grounded thermocouples or millivolt sensors, this is at the sensor end.
For insulated/ungrounded thermocouples, this is at the module end. Contact your

sensor manufacturer for additional details.

• If it is necessary to connect the shield drain at the module end, connect it to earth

ground using a panel or DIN rail mounting screw.

• Routing the field wiring in a grounded conduit can further reduce electrical noise.

Terminal Block Layout

Labeling the Terminals

A write-on label is provided with the module. Mark the identification of each terminal with
permanent ink, and slide the label back into the door.

IN1 -

IN1 +

IN 0 -

IN 0 +

IN2 -

IN2 +

CJC

CJC

IN3 -

IN3 +