16 MicroLogix 1200 Thermocouple/mV Input Module

Publication 1762-IN013B-EN-P - June 2013

Module Configuration Word

Word 4 of the configuration data file contains the Enable/Disable Cyclic Calibration bit as
shown in the table below.

Specifications

To Select

Make these bit settings

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Cyclic
Calibration

Enabled

(1)

(1)

When enabled, an autocalibration cycle is performed on all enabled channels every 5 minutes.

0

Disabled

1

General Specifications

Specification

Value

Dimensions, (H x W x D)

90 x 40 x 87 mm (height including mounting tabs is 110 mm)
3.54 x 1.58 x 3.43 in. (height including mounting tabs is 4.33 in.)

Approximate Shipping Weight

(with carton)

220 g (0.53 lbs.)

Temperature, nonoperating

-40…85 °C (-40…185°F)

Temperature, operating

0…55 °C (-32…131 °F)

Humidity, operating

5…95% non-condensing

Altitude, operating

2000 m (6561 ft)

Vibration, operating

10…500 Hz, 5 g, 0.030 in. max. peak-to-peak

Shock, operating

30 g

Vendor ID code

1

Product type code

10

Product code

64

Hazardous environment class

Class I, Division 2, Hazardous Location, Groups A, B, C, D

ISA/ANSI 12.12.01

(C-UL under CSA C22.2 No. 213)

Noise immunity

NEMA standard ICS 2-230

Radiated and conducted emissions

EN50081-2 Class A

ESD immunity (EN61000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated immunity (EN61000-4-3)

10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz
keyed carrier

Fast transient burst (EN61000-4-4)

2 kV, 5 kHz

Surge immunity (EN61000-4-5)

1 kV galvanic gun

Conducted immunity (EN61000-4-6)

10V, 0.15 …80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is
30…1000 MHz.

Advertising