MicroLogix 1200 Thermocouple/mV Input Module 19
Publication 1762-IN013B-EN-P - June 2013
Channel Update Time
Filter Frequency Selection
Channel Update Time
10 Hz
303 ms
50 Hz
63 ms
60 Hz
53 ms
250 Hz
15 ms
500 Hz
9 ms
1 kHz
7 ms
Repeatability
Input Type
Repeatability for 10 Hz Filter at 25°C
[77°F]
Themocouple J
±0.1 °C [±0.18 °F]
Themocouple N (-110…1300 °C [-166…2372 °F])
±0.1 °C [±0.18 °F]
Themocouple N (-210…-110 °C [-346…-166 °F])
±0.25 °C [±0.45 °F]
Themocouple T (-170…400 °C [-274…752 °F])
±0 .1 °C [±0.18 °F]
Themocouple T (-270…-170 °C [-454…-274 °F])
±1.5 °C [±2.7 °F]
Themocouple K (-270…1370 °C [-454…2498 °F])
±0.1 °C [±0.18 °F]
Themocouple K (-270…-170 °C [-454…-274 °F])
±2.0 °C [±3.6 °F]
Themocouple E (-220…1000 °C [-364…1832 °F])
±0.1 °C [±0.18 °F]
Themocouple E (-270…-220 °C [-454…-364 °F])
±1.0 °C [±1.8 °F]
Themocouples S and R
±0.4 °C [±0.72 °F]
Themocouple C
±0.2 °C [±0.36 °F]
Themocouple B
±0.7 °C [±1.26 °F]
±50 mV
±6
μV
±100 mV
±6
μV