Mounting, Minimum spacing – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 6

Advertising
background image

6 MicroLogix 1200 Thermocouple/mV Input Module

Publication 1762-IN013B-EN-P - June 2013

Mounting

Minimum Spacing

Maintain spacing from enclosure
walls, wireways, adjacent
equipment, etc. Allow 50.8 mm
(2 in.) of space on all sides for
adequate ventilation, as shown:

ATTENTION

Do not remove protective debris strip until after the module and all other
equipment near the module is mounted and wiring is complete. Once
wiring is complete and the module is free of debris, carefully remove
protective debris strip. Failure to remove strip before operating can cause
overheating.

TIP

1762 expansion I/O may be mounted horizontally only.

ATTENTION

During panel or DIN rail mounting of all devices, be sure that all debris
(metal chips, wire strands, etc.) is kept from falling into the module.
Debris that falls into the module could cause damage when power is
applied to the module.