MicroLogix 1200 Thermocouple/mV Input Module 21

Publication 1762-IN013B-EN-P - June 2013

North American Hazardous Location Approval

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous
locations only.

The following WARNING statement applies to use in hazardous locations.

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l’utilisation de cet équipement
en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C, D,
Hazardous Locations and nonhazardous locations
only. Each product is supplied with markings on the
rating nameplate indicating the hazardous location
temperature code. When combining products within a
system, the most adverse temperature code (lowest
"T" number) may be used to help determine the
overall temperature code of the system. Combinations
of equipment in your system are subject to
investigation by the local Authority Having
Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.

WARNING

EXPLOSION HAZARD

• Substitution of components may

impair suitability for Class I, Division
2.

• Do not replace components or

disconnect equipment unless power
has been switched off.

• Do not connect or disconnect

components unless power has been
switched off.

• This product must be installed in an

enclosure.

• In Class I, Division 2 applications, the

bus connector must be fully seated
and the bus connector cover must be
snapped in place.

• In Class I, Division 2 applications, all

modules must be mounted in direct
contact with each other as shown on
page 7. If DIN rail mounting is used,
an end stop must be installed ahead
of the controller and after the last
1762 I/O module.

• All wiring must comply with N.E.C.

article 501-4(b).

• The interior of the enclosure must be

accessible only by the use of a tool.

• For applicable equipment (relay

modules, etc.), exposure to some
chemicals may degrade the sealing
properties of materials used in the
following devices: Relays, Epoxy. It is
recommended that the User
periodically inspect these devices for
any degradation of properties and
replace the module if degradation is
found.

AVERTISSEMENT

RISQUE D’EXPLOSION

• La substitution de composants peut

rendre cet équipement impropre à une
utilisation en environnement de Classe
1, Division 2.

• Ne pas remplacer de composants ou

déconnecter l'équipement sans s'être
assuré que l'alimentation est coupée.

• Ne pas connecter ou déconnecter des

composants sans s'être assuré que
l'alimentation est coupée.

• Ce produit doit être installé dans une

armoire.

• Pour les applications de Classe I,

Division 2, le connecteur de bus doit
être correctement installé et son
couvercle enclenché.

• Pour les applications de Classe 1,

Division 2, tous les modules doivent
être installés en contact direct les uns
avec les autres, comme indiqué page 6.
Si on utilise le montage sur rail DIN,
une butée doit être placée à l'avant de
l'automate et après la dernière unité
d'E/S 1762.