Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 17

Advertising
background image

MicroLogix 1200 Thermocouple/mV Input Module 17

Publication 1762-IN013B-EN-P - June 2013

Input Specifications

Specification

1762-IT4

Number of Inputs

4 input channels plus a CJC sensor

Resolution

15 bits plus sign

Bus Current Draw, max

40 mA @ 5V DC

50 mA @ 24V DC

Heat Dissipation

1.5 Total Watts (The Watts per point, plus the minimum Watts, with all
points energized.)

Converter Type

Delta Sigma

Input Filtering

Programmable notch filter with 10, 50, 60, 250, 500 and 1k Hz
frequencies.

Channel Update Time

Input filter and configuration dependent.

See

“Channel Update Time” on page 19

Rated Working Voltage

(1)

30V AC/30V DC

Common Mode Voltage Range

(2)

±10V DC maximum per channel

Common Mode Rejection

115 dB (minimum) @ 50 Hz (with 10 Hz or 50 Hz filter)

115 dB (minimum) @ 60 Hz (with 10 Hz or 60 Hz filter)

Normal Mode Rejection Ratio

85 dB (minimum) @ 50 Hz (with 10 Hz or 50 Hz filter)

85 dB (minimum) @ 60 Hz (with 10 Hz or 60 Hz filter)

Cable Impedance, max

25

Ω

Input Impedance

>10 M

Ω

Open-circuit Detection Time (max.)

7 ms…1.515 seconds

(4)

Calibration

The module performs autocalibration upon power-up and whenever a
channel is enabled. You can also program the module to calibrate every
five minutes using the Enable/Disable Cyclic Calibration bit.

Repeatability

(3)

See

“Repeatability” on page 19

Maximum Overload at Input
Terminals

±35V DC continuous

(5)

Module Error over Full Temperature
Range

(0…55°C [+32…131°F])

See

“Input Accuracy” on page 18

CJC Accuracy

±1.3 °C (±2.34 °F)

Power Supply Distance Rating

6 (The module may not be more than 6 modules away from the system
power supply.)

Input Group to Bus Isolation

720V DC for 1 minute (qualification)

30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)

Input Channel Configuration

via configuration software screen or the user program (by writing a
unique bit pattern into the module’s configuration file).

Module OK LED

On: module has power, has passed internal diagnostics, and is
communicating over the bus.

Off: Any of the above is not true.

Channel Diagnostics

Over- or under-range and open-circuit by bit reporting