Interpret the led indicators – Rockwell Automation 1790D-XXXX DeviceNet Digital Base D-Shell Module CompactBlock LDX I/O User Manual
Page 16

16 DeviceNet Digital Base D-Shell Block CompactBlock LDX I/O
Publication
1790-IN007C-EN-P - May 2006
Interpret the LED Indicators
Read this section for information about how to interpret block LED
indicators and related procedures.
For a module status indicator that is flashing red, refer to the cable
break procedure section.
The base block has the following indicators.
• Block status
• Network status
• I/O status
Indication
Probable Cause
Recommended Action
Module Status
Solid Red
Unrecoverable fault in base unit.
Replace base block.
Flashing Red
Fault in expansion unit.
Replace expansion unit.
Solid Green
Normal operation.
None.
Off
No power.
Apply power to device.
Network Status
Solid Red
Module node number is a duplicate of an
existing node, or network
communication issues exist.
Change module node
number to an unused
address, or verify
network wiring is correct
and communication is
stable.
Flashing Red
An I/O connection has timed out.
Cycle power to the
module.