Rockwell Automation 1790D-XXXX DeviceNet Digital Base D-Shell Module CompactBlock LDX I/O  User Manual

Page 22

Advertising
background image

22 DeviceNet Digital Base D-Shell Block CompactBlock LDX I/O

Publication

1790-IN007C-EN-P - May 2006

Environmental Specifications Common To All Base Blocks in This Publication

Attribute

Value

North American Temp Code

T5

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0...55 °C (32...131 °F)

Storage Temperature

IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock)
-40...85 °C (-40...185 °F)

Relative Humidity

IEC60068-2-30 (Test Db, Unpackaged Damp Heat)
5...90% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10…500 Hz

Shock, Operating

IEC60068-2-27 (Test Ea, Unpackaged Shock) 10 g

Shock, Nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock) 30 g

Emissions

CISPR 11: Group 1, Class A

ESD Immunity

IEC6100-4-2 - 8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz

EFT/B Immunity

IEC 61000-4-4
+1 kV at 5 kHz on power ports
+2 kV at 5 kHz on signal ports
+2 kV at 5 kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:
±1 kV line-line (DM) on power ports
±1 kV line-line (DM) on signal ports
±2 kV line-earth (CM) on communications ports

Conducted RF Immunity

IEC61000-4-6
10V rms with 1 kHz sine-wave 80%AM at 150 kHz...80 MHz