24 CompactLogix ControlNet Interface Module

Publication

1768-IN006A-EN-P - September 2007

Interpreting the Status Indicators

Module Status Display Descriptions

Status

Display

Cause

Action

Off

None

The module is not
communicating due to a
power supply fault or
internal fault.

1. Check the power supply.
2. Check the cable connectors.
3. Make sure the module is firmly

seated in the chassis.

4. Replace the module if the indicator

remains off.

Red

Msg
scrolls

The module’s network
address is set to 00, an
invalid ControlNet network
address.

If switches are set to 00 the
display scrolls: FAULT:
ADDRESS SWITCHES = 00,
ILLEGAL.

1. Turn chassis power supply off.
2. Remove the module from the

chassis.

3. Set the network address switches

to a unique address, 01…99.

4. Install the module in the chassis.
5. Turn chassis power supply on if it's

off.

BPA#
ERR

The module detected a
different slot address from
that latched in when you
cycled power. Excessive
noise on the backplane
causes this error.

Replace the chassis or module.

BPRX
ERR

There are too many CRC
errors being generated by
the multicast backplane
receiver, so the backplane
multicast receivers have
been shut off.

Replace the module.

BPIC

ERR

There is a hardware fault

within the module.

Replace the module.

CNIC

ERR

OK