Rockwell Automation 1768-CNBR CompactLogix ControlNet Communication Module Installation Instructions User Manual
Page 25
 
CompactLogix ControlNet Interface Module 25
Publication
1768-IN006A-EN-P - September 2007
Red
DUPL 
NODE
The module’s network 
address is the same as 
another module’s on the link.
1. Turn chassis power supply off.
2. Remove the module from the 
chassis.
3. Set the network address switches
to a unique address, 01…99.
4. Install the module in the chassis.
5. Turn chassis power supply on if it's 
off.
RACK 
ERR
Cannot read backplane 
EEPROM, or rack/slot 
address incorrect.
Replace the chassis.
Flashing 
red
BOOT
The module has invalid 
firmware.
Update module firmware with 
ControlFlash Update Utility.
ROM
UPDT
Flash update is in progress.
None required.
SNGL 
KPR!
The module detected that it 
has been connected to a 
ControlNet 1.5 
(single-keeper) network.
Update the module’s firmware at MAC 
ID 01 and reschedule the network.
Green
OK
Normal operation.
None required.
INIT
The module is initializing.
BW 
>MAX
The module is receiving too 
much network traffic and 
connections are timing out. 
The network bandwidth has 
been exceeded.
None (temporary condition).
If this happens frequently, add another 
1768-CNB or 1768-CNBR module and 
split the traffic between them.
Module Status Display Descriptions
Status
Display
Cause
Action
OK