Rockwell Automation 1768-CNBR CompactLogix ControlNet Communication Module Installation Instructions User Manual

Page 25

Advertising
background image

CompactLogix ControlNet Interface Module 25

Publication

1768-IN006A-EN-P - September 2007

Red

DUPL
NODE

The module’s network
address is the same as
another module’s on the link.

1. Turn chassis power supply off.
2. Remove the module from the

chassis.

3. Set the network address switches

to a unique address, 01…99.

4. Install the module in the chassis.
5. Turn chassis power supply on if it's

off.

RACK
ERR

Cannot read backplane
EEPROM, or rack/slot
address incorrect.

Replace the chassis.

Flashing
red

BOOT

The module has invalid
firmware.

Update module firmware with
ControlFlash Update Utility.

ROM

UPDT

Flash update is in progress.

None required.

SNGL
KPR!

The module detected that it
has been connected to a
ControlNet 1.5
(single-keeper) network.

Update the module’s firmware at MAC
ID 01 and reschedule the network.

Green

OK

Normal operation.

None required.

INIT

The module is initializing.

BW
>MAX

The module is receiving too
much network traffic and
connections are timing out.
The network bandwidth has
been exceeded.

None (temporary condition).

If this happens frequently, add another
1768-CNB or 1768-CNBR module and
split the traffic between them.

Module Status Display Descriptions

Status

Display

Cause

Action

OK