ControlNet Network Channel-status Indicators
The ControlNet network channel-status indicators appear in one of the 
following states:
• Steady - indicator is on continuously in the defined state.
• Alternating - the two indicators alternate between the two defined 
states at the same time (applies to both indicators viewed together). 
The two indicators are always in opposite states, out of phase.
• Flashing - the indicator alternates between the two defined states
(applies to each indicator viewed independent of the other). If both 
indicators are flashing, they must flash together, in phase.
The ControlNet Network Channel Status Indicators table summarizes the 
meanings of these states.
ControlNet Network Channel-status Indicators
Cause
Action
Off
No power
None or apply power.
Steady red
Faulted unit
Cycle power or reset unit.
If fault persists, contact 
Allen-Bradley representative or 
distributor.
Alternating 
red/green
Self-test
None.
Alternating red/off Incorrect node configuration
Check network address and other 
ControlNet network configuration 
parameters.
Off
Channel disabled
Program network for redundant 
media, if required.
Steady green
Normal operation
None.
or
A
B