26 CompactLogix ControlNet Interface Module

Publication

1768-IN006A-EN-P - September 2007

Green

SW

ERR

The node address switch
changed after cycling power.

None required, but we recommend
that you either return switches to their
original settings or replace the
module, since this could indicate a
hardware problem.

Flashing
green

CNFG
ERR

ControlNet network
configuration error.

Recheck configuration.

NET

ERR

Network cabling error or no
other active nodes on the
network.

Recheck your network cabling and
make sure another node on the
network is active (online).

Module Status Display Descriptions

Status

Display

Cause

Action