Enhanced PLC-5 Programmable Controllers 13

Install the PLC-5 Programmable Controller

The controller is a modular component of the 1771 I/O system requiring a
properly installed system chassis. Refer to publication 1771-IN075 for detailed
information on acceptable chassis along with proper installation and
grounding requirements. Limit the maximum adjacent slot power dissipation
to 10W.

1. Define the DH+ Station Address of Channel 1A by setting switch

assembly SW-1 on the back of the controller. See the side of the
controller if you want to use another address.

2. Specify the digital interface of Channel 0.

side view of controller

side view

1 2 3 4 5

6 7

up
230 Kbaud

down
57.6 Kbaud

For series E and later controllers:
use this switch to select baud rate
For series D and earlier controllers:
this switch is always off

Front of
Controller

1 2 3 4 5 6 7 8 9 10

bottom view of PLC-5/20 controller

bottom view of PLC-5/40 and -5/80 controller

side view

OFF

Front of
Controller

1 2 3 4 5 6 7 8 9 10