Troubleshoot the controller – Rockwell Automation 1785-l11B, -L20B, -L30B, -L40B, -L40L, -L60B, -L60L, -L80B Enhanced PLC-5 Programmable Controllers Installation Instructions User Manual
Page 17

Publication 1785-IN062A-EN-P - May 2005
Enhanced PLC-5 Programmable Controllers 17
Troubleshoot the Controller
Use the controller’s status indicators with the following tables for diagnostics
and troubleshooting.
Indicator
Color
Description
Probable Cause
Recommended Action
BATT
Red
Battery low
Battery low
Replace battery within 10 days
Off
Battery is good
Normal operation
No action required
PROC
Green
(steady)
Processor is in run
mode and fully
operational
Normal operation
No action required
Green
(blinking)
Processor memory is
being transferred to
EEPROM
Normal operation
No action required
Red
(blinking)
Major fault
RSLogix 5
download in
progress
Run-time error
During RSLogix 5 download, this
is normal operation - wait for
download to complete.
If not during RSLogix 5 download:
Check major fault bit in status file
(S:11) for error definition
Clear fault, correct problem, and
return to run mode
Alternating
Red and
Green
Processor in
FLASH-memory
programming mode
Normal operation if
processor's FLASH
memory is being
reprogrammed
No action required - allow flash
update to complete
Continued on next page
BATT
PROC
FORCE
COMM