22 Enhanced PLC-5 Programmable Controllers
Battery Type
Enhanced PLC-5 programmable controllers use 1770-XYC batteries that
contain 0.65 grams of lithium.
Average Battery Lifetime Specifications
Worst-case battery life estimates
In this controller:
At this
temperature:
Power off
100%
Power off
50%
Battery duration
after the LED lights
1
PLC-5/11, -5/20
60°C
256 days
1.4 years
11.5 days
25°C
2 years
4 years
47 days
PLC-5/30, -5/40, -5/40L,
-5/60, -5/60L, -5/80
60°C
84 days
150 days
5 days
25°C
1 year
1.2 years
30 days
1
The battery indicator (BATT) warns you when the battery is low. These durations are based on the battery supplying the
only power to the controller (power to the chassis is off) once the LED first lights.