Enhanced PLC-5 Programmable Controllers 15

Install the I/O Modules

For more information, see the installation instructions or user manual for the
particular module you are installing.

Apply Power to the System

Apply power to the system. Check the LED display on the controller. If your
system is operating properly, the PROC LED should be steady red and the
message

“Processor RAM is faulted. Press <Enter> to clear

memory”

should appear on the programming software display. See the

following table to proceed. If the PROC LED is not off, turn to the next page
for troubleshooting information.

If your keyswitch is in
this position:

Do this:

PROGRAM

Clear memory. The PROC LED should turn off.

The software is in Program mode.

REMOTE

Clear memory. The PROC LED should turn off.

The software is in Remote Program mode.

RUN

You see the message “

No access or privilege

violation

” because you cannot clear memory in Run

mode. Change the keyswitch position to Program or Remote
and press <Enter> to clear memory.

Locking
Bar

Card Guides

20618-M

Install each I/O module
and connect the wiring arm.