Rockwell Automation 1785-l11B, -L20B, -L30B, -L40B, -L40L, -L60B, -L60L, -L80B Enhanced PLC-5 Programmable Controllers Installation Instructions User Manual

Page 8

Advertising
background image

Publication 1785-IN062A-EN-P - May 2005

8 Enhanced PLC-5 Programmable Controllers

PLC-5/40, -5/46, -5/60, -5/80, and -5/86 Controller Front Panels

Additional System Components

Along with your Enhanced PLC-5 programmable controller, you need the
following components to complete a basic system:

Use this port with ASCII or DF1 full-duplex, half-duplex
master, and half-duplex slave protocols. The port's
default configuration supports controller programming:

one stop-bit
BCC error check
no handshaking

DF1 point-to-point
2400 bps
no parity

keyswitch; selects controller mode

8-pin mini-DIN, DH+ programming
terminal connection parallel to channel
2A when channel 2A is configured for
DH+ communications

channel 2A communication port;
its default configuration is unused

channel 2B communication port;
its default configuration is unused

channel 1A communication port;
its default configuration is DH+

channel 1B communication port;
its default configuration is remote I/O scanner

Install battery here

battery indicator (red when the battery is low)

processor RUN/FAULT indicator (green when
running; red when faulted)

force indicator (amber when I/O forces are enabled)

channel 0 communication status indicator
(green when the channel is communicating)

channel 1B status indicator (lights green and red)

PLC-5 family member designation

channel 0-25-pin D-shell serial port; supports standard
EIA RS-232C and RS-423 and is RS-422A compatible

Install memory module here

Use these labels to write information about the
channel: communication mode, station addresses etc.

channel 2B status indicator (lights green and red)

channel 2A status indicator
(lights green and red)

8-pin mini-DIN, DH+ programming terminal
connection parallel to channel 1A

channel 1A status indicator
(lights green and red)

Product name

Cat. No.

lithium battery

1770-XYC

I/O chassis

1771-A1B, -A2B, -A3B, -A3B1, -A4B

power supply

1771-P4S, -P6S, -P4S1, -P6S1

personal computer

IMPORTANT

In this document, we assume you are using a brand-new
Enhanced PLC-5 programmable controller.