Publication 1785-IN062A-EN-P - May 2005

18 Enhanced PLC-5 Programmable Controllers

Indicator

Color

Description

Probable Cause

Recommended Action

PROC

Red

(steady)

Fault with memory
loss

New controller

Processor has failed
internal diagnostics

Use programming software to
clear and initialize memory

Install battery (to preserve failure
diagnostics), then power down,
reseat controller and power up;
then reload your program. If you
are unable to reload your
program, replace the controller.

If you are able to reload your
program and fault persists,
contact Technical Support at
440.646.3223 to diagnose the
problem.

Off

Processor is in
program load or test
mode or is not
receiving power

Power supply or
connections

Check power supply and
connections

FORCE

Amber

(steady)

SFC and/or I/O forces
enabled

Normal operation

No action required

Amber
(blinking)

SFC and/or I/O forces
present but not
enabled

Off

SFC and/or I/O forces
not present

COMM

Off

No transmission on
channel 0

Normal operation if
channel is not being
used

No action required

Green
(blinking)

Transmission on
channel 0

Normal operation if
channel is being
used

BATT