Configuring Your Module

You configure your output/input module by setting bits in the configuration word.

Data Table – 1794-IE12

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read Words
0 - Input 0

Signed 2’s Complement data Value of Channel 0

1 - Input 1

Signed 2’s Complement data Value of Channel 1

2 - Input 2

Signed 2’s Complement data Value of Channel 2

3 - Input 3

Signed 2’s Complement data Value of Channel 3

4 - Input 4

Signed 2’s Complement data Value of Channel 4

5 - Input 5

Signed 2’s Complement data Value of Channel 5

6 - Input 6

Signed 2’s Complement data Value of Channel 6

7 - Input 7

Signed 2’s Complement data Value of Channel 7

8 - Input 8

Signed 2’s Complement data Value of Channel 8

9 - Input 9

Signed 2’s Complement data Value of Channel 9

10 - Input 10

Signed 2’s Complement data Value of Channel 10

11 - Input 11

Signed 2’s Complement data Value of Channel 11

12 - Status

PU

FP

GF

NU R11 R10 R9

R8

R7 R6 R5 R4 R3 R2 R1 R0

Write Words
0 - Reserved

EN 0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1 - Configuration QS 0

0

0

CAB

C89

C67

C45

C23

C01

Where:
PU = Power up bit

FP = Field power fault

GF = General fault

NU = Not used

Rx = Out of range (x = associated channel)

EN = Enable

QS = Quick step bit – allows input filter to be reduced during rapid signal changes.
Cxx = Configuration