North american hazardous location approval – Rockwell Automation 1794-IE8XOE4 FLEX I/O DC Input, Output, and Input/Output Analog Modules Installation User Manual

Page 5

Advertising
background image

FLEX I/O DC Input, Output, and Input/Output Analog Modules 5

Publication 1794-IN106D-EN-E - January 2014

North American Hazardous Location Approval

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l’utilisation de cet équipement
en environnements dangereux:

Products marked CL I, DIV 2, GP A, B, C, D are suitable for
use in Class I Division 2 Groups A, B, C, D, hazardous
locations and nonhazardous locations only. Each product
is supplied with markings on the rating nameplate
indicating the hazardous location temperature code.
When combining products within a system, the most
adverse temperature code (lowest “T” number) may be
used to help determine the overall temperature code of
the system. Combinations of equipment in your system
are subject to investigation by the local Authority Having
Jurisdiction at the time of installation.

Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent
qu’à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livré avec des marquages sur sa plaque d’identification qui
indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les combinaisons
d’équipements dans le système sont sujettes à inspection par
les autorités locales qualifiées au moment de l’installation.

WARNING: EXPLOSION
HAZARD

• Do not disconnect equipment

unless power has been removed or
the area is known to be
nonhazardous.

• Do not disconnect connections to

this equipment unless power has
been removed or the area is known
to be nonhazardous. Secure any
external connections that mate to
this equipment by using screws,
sliding latches, threaded
connectors, or other means
provided with this product.

• Substitution of components may

impair suitability for Class I,
Division 2.

• If this product contains batteries,

they must only be changed in an
area known to be nonhazardous.

WARNING: RISQUE
D’EXPLOSION

• Couper le courant ou s’assurer que

l’environnement est classé non
dangereux avant de débrancher
l'équipement.

• Couper le courant ou s'assurer que

l’environnement est classé non
dangereux avant de débrancher les
connecteurs. Fixer tous les connecteurs
externes reliés à cet équipement à l'aide
de vis, loquets coulissants, connecteurs
filetés ou autres moyens fournis avec ce
produit.

• La substitution de composants peut

rendre cet équipement inadapté à une
utilisation en environnement de Classe I,
Division 2.

• S’assurer que l’environnement est classé

non dangereux avant de changer les
piles.