Specifications – Rockwell Automation 1794-IE8XOE4 FLEX I/O DC Input, Output, and Input/Output Analog Modules Installation User Manual

Page 15

Advertising
background image

FLEX I/O DC Input, Output, and Input/Output Analog Modules 15

Publication 1794-IN106D-EN-E - January 2014

Specifications

General Specifications for the 1794-IE12, 1794-OE12, and 1794-IE8XOE4 Modules

Attribute

1794-IE12

1794-OE12

1794-IE8XOE4

Indicators

1 red/green power/status indicator

Recommended

terminal base

1794-TB3G or 1794-TB3GS

FLEXBus current

80 mA

Power supply

Voltage, nom.(nom)
Specification

Certification
Voltage, range

24V DC

(2)

24V DC

10.5...31.2V DC

(2)

includes 5 % AC ripple

24V DC

(2)

24V DC

10.0...31.2V DC

24V DC

(2)

24V DC

10.0...31.2V DC

Supply current
Specification

Certification

30 mA @ 24V DC;
45 mA @ 10.0V DC

60 mA

320 mA @ 24V DC;
720 mA @ 10.0V DC

320 mA

140 mA @ 24V DC;

280 mA @ 10.0V DC

140 mA

Calibration

None required – factory calibrated

Isolation voltage

50V (continuous), Basic Insulation Type,
No isolation between individual channels
Type tested @ 850V AC for 60 s between field and system

Power dissipation, max 1.2 W @ 31.2V DC

7.68 W @ 24V DC

3.4 W @ 24V DC

Thermal dissipation

4.1 BTU/hr @ 31.2V DC 26.2 BTU/hr @ 24V DC 11.6 BTU/hr @ 24V DC

Terminal base

screw torque

0.8 Nm (7 lb-in.)
1.0 Nm (9 lb-in.) – 1794-TBN only

Wire type

Shielded

Wire size

Determined by installed terminal base

Wiring category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-IN041

.

2 – on signal ports
2 – on power ports

North American
temperature code

T4A

Dimensions (approx.)

(HxWxD)

46 x 94 x 54 mm

(1.81 x 3.7 x 2.1 in.)

Enclosure type rating

None (open-style)

Keyswitch position

3

4

5

Advertising