FLEX I/O DC Input, Output, and Input/Output Analog Modules 9

Publication 1794-IN106D-EN-E - January 2014

Wire Connections for the 1794-OE12/A Analog Output Module

Channel

Signal Type

Label
Marking

1794-TB3G or 1794-TB3GS
Output

Common Terminal

Output 0

Current

I0

A-0

B-17

Voltage

V0

A-1

Output 1

Current

I1

A-2

B-18

Voltage

V1

A-3

Output 2

Current

I2

A-4

B-23

Voltage

V2

A-5

Output 3

Current

I3

A-6

B-24

Voltage

V3

A-7

Output 4

Current

I4

A-8

B-25

Voltage

V4

A-9

Output 5

Current

I5

A-10

B-26

Voltage

V5

A-11

Output 6

Current

I6

A-12

B-31

Voltage

V6

A-13

Output 7

Current

I7

A-14

B-32

Voltage

V7

A-15

Output 8

Current

I8

B-19

C-37

Voltage

V8

B-20

Output 9

Current

I9

B.21

C-39

Voltage

V9

B-22

Output 10

Current

I10

B-27

C-46

Voltage

V10

B-28

Output 11

Current

I11

B-29

C-48

Voltage

V11

B-30

-V DC
Common

1794-TB3G and 1794-TB3GS – Terminals C-35 and C-51 are internally
connected in the terminal base unit.

+V DC Power

1794-TB3G and 1794-TB3GS – Terminals C-34 and C-50 are internally
connected in the terminal base unit.

Chassis
Ground
(Shield)

1794-TB3G and 1794-TB3GS – Terminals B-16, B-33, C-38, C-40...C-45, and
C-47 are internally connected to chassis ground.

ATTENTION: Use shielded cable for better noise immunity and easier
connection to ground. Connect shield to designated ground points on the
terminal base unit. Ground at the terminal base unit only.