FLEX I/O DC Input, Output, and Input/Output Analog Modules 7

Publication 1794-IN106D-EN-E - January 2014

Connect Wiring

Connect the wiring for the 1794-TB3G and 1794-TB3GS terminal bases as shown in the
following figure:

Terminal Base Wiring for the 1794-IE12/A Analog Input Module

ATTENTION: To reduce susceptibility to noise, power analog modules and
digital modules from separate power supplies. Do not exceed a length of

10 m (33 ft) for DC power or analog I/O cabling.

ATTENTION: Do not daisy-chain power or ground from this terminal base
unit to any AC or DC digital module terminal base units.

ATTENTION: Do not exceed a length of 10 m (33 ft) for signal cabling.

I = Current

[1794-TB3G shown]

V=Voltage
C-0...C-11 = Returns for I or V connections 0...11
+24V DC = Terminals C-34 and C-50
COM = Terminals C-35 and C-51
Chassis ground (CG) = Terminals B-16, B-33, C-38, C-40...C-45, C-47
NC = No connection
For daisy-chaining: Supply in – C-34 (+) and C-35 (-)
Supply out – C-50 (+) and C-51 (-)

24V DC
Supply In

24V DC
Supply Out

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Chassis
Ground

Chassis
Ground

+V COM

+V COM

Chassis Grounds for Shields

A

B

C

NC

I0

I1

I2

I3

I4

I5

I6

I7

I8

I9

I10

I11

V0

V1

V2

V3

V4

V5

V6

V7

V8

V9

V10

V11

C0 C1

C2 C3 C4 C5

C6 C7

C8

C9

C10

C11

NC

NC

NC

Advertising