Range Selection Bits for the 1794-IE12, 1794-OE12, and 1794-IE8XOE4

Safe State Selection Bits for the 1794-OE12 and 1794-IE8XOE4

When EN = 0, these bits designate the source of the safe state data for all outputs in

the module.

Range

Out of Range

Range Setting

Cxx

(1)

Channel Configuration

(1)

xx = associated channel pair

-10...+10V DC

< -10.0V or > 10.0V

Set bits for each
channel pair

00 = off

01 = 0...20 mA

10 = 4...20 mA

11 = +10V

C01 for channels 0 and 1

C23 for channels 2 and 3

C45 for channels 4 and 5

C67 for channels 6 and 7

C89 for channels 8 and 9

CAB for channels 10 and 11

4...20 mA

< 4.0mA or > 20.0 mA

0...20 mA

< 0.0 mA or > 20.0 mA

S1/S0 Safe State
Select Source

Safe State Mode

Safe State Output Behavior

S1

S0

0

0

Safe State value is in the
output words

Outputs will use Safe State value

0

1

Reserved (Safe State value
is in the output words)

Reserved (Outputs will use Safe State
value)

1

0

Clear/Reset the outputs,
based on range selected

+10V range – Output set to 0V

4...20 mA range – Output set to 4 mA

0...20 mA range – Output set to 0 mA

1

1

Hold output at its present
level

Outputs will Hold Last State