Data table – 1794-ie8xoe4 – Rockwell Automation 1794-IE8XOE4 FLEX I/O DC Input, Output, and Input/Output Analog Modules Installation User Manual

Page 14

Advertising
background image

14 FLEX I/O DC Input, Output, and Input/Output Analog Modules

Publication 1794-IN106D-EN-E - January 2014

Data Table – 1794-IE8XOE4

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read Words
0 - Input 0

Signed 2’s Complement data Value of Channel 0

1 - Input 1

Signed 2’s Complement data Value of Channel 1

2 - Input 2

Signed 2’s Complement data Value of Channel 2

3 - Input 3

Signed 2’s Complement data Value of Channel 3

4 - Input 4

Signed 2’s Complement data Value of Channel 4

5 - Input 5

Signed 2’s Complement data Value of Channel 5

6 - Input 6

Signed 2’s Complement data Value of Channel 6

7 - Input 7

Signed 2’s Complement data Value of Channel 7

8 - Status

PU

FP

GF

NU W3 W2 W1 W0 R7 R6 R5 R4 R3 R2 R1 R0

Write Words
0 - Reserved

EN S1

S0

WR 0

0

0

0

0

0

0

0

0

0

0

0

1 - Output 0

Signed 2’s Complement data Value of Channel 0

2 - Output 1

Signed 2’s Complement data Value of Channel 1

3 - Output 2

Signed 2’s Complement data Value of Channel 2

4 - Output 3

Signed 2’s Complement data Value of Channel 3

5 - Configuration QS 0

0

0

CAB

C89

C67

C45

C23

C01

Where:

PU = Power up bit
FP = Field power fault
GF = General fault
NU = Not used
Wx = Wire off (x = associated channel)
Rx = Out of range (x = associated channel)
EN = Enable outputs
S1/S0 = Safe state source – When EN = 0, these bits indicate source of safe state output.
WR = Wire-off reset
QS = Quick step bit – allows input filter to be reduced during rapid signal changes.
Cxx = Channel Configuration (xx = associated channel pair)