Analog Output Module

11

Publication 1771-IN044C-EN-P - October 2002

Ground the Chassis and Module

Use the following diagrams to ground your
I/O chassis and analog input module. Follow
these steps to prepare the cable:

Refer to Wiring and Grounding Guidelines,
publication 1770-4.1 for additional
information.

Remove a length of cable

jacket from the Belden 8761 cable.

Pull the foil shield and bare

drain wire from the insulated wires.

Bare drain

wire

Insulated

wires

Foil

shield

Twist the foil shield and drain

wire together to form a single strand.

Attach a ground lug.

Belden 8761 Cable

2

When using shielded cable wire, ground the foil shield

and drain wire only at one end of the cable. We recomĆ

mend that you wrap the foil shield and drain wire toĆ

gether and connect them to a chassis mounting bolt.

At the opposite end of the cable, tape exposed shield

and drain wire with electrical tape to insulate it from

electrical contact.

1

3

4

ExternalĆtooth

Washers

#10 ThreadĆforming screw

Shield and Drain

twisted together

SingleĆpoint Grounding

Extend shield to termination point.

Expose just enough cable to adequately

terminate inner conductors.

Use heat shrink tubing

or other suitable insulaĆ

tion where wire exits

cable jacket.

Grounding Stud

1

Use the cup washer if crimpĆon lugs are not used.

Chassis Ground
When you connect grounding conductors to the I/O chassis

grounding stud, place a star washer under the first lug, then

place a nut with captive lock washer on top of each ground lug.

Torque the nut with captive washer to 18(+3) pound-inches.

Ground Lug

Ground Lug

1

Star

Washer

I/O Chassis

Side Plate

Nut and Captive

Washer

Shield and Drain

twisted together

Nut