Analog Output Module

18

Publication 1771-IN044C-EN-P - October 2002

Value

Description

Enclosure Type Rating

None (open-style)

Keying

Between 10 and 12

Between 26 and 28

Field Wiring Arm

Catalog No. 1771ĆWC

Field Wiring Arm Screw Torque

7-9 pound-inches (0.6-0.7Nm)

Conductors

Wire Size

Category

12 gauge (4mm

2

) maximum stranded copper wire,

(Belden 8761)

3/64 inch (1.2mm) insulation maximum

2

1

Certifications

(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment for

Class I, Division 2 Group A, B, C, D Hazardous

Locations

CSA

CSA Certified Process Control Equipment

CE

2

European Union 89/336/EEC EMC Directive,

compliant with:

EN61000-6-4, Industrial Emissions

EN50082-2, Industrial Immunity

EN61326, Meas./Control/Lab., Industrial

Requirements

EN61000-6-2, Industrial Immunity

EEx

2

European Union 94/9/EEC ATEX Directive, compliant

with:

EN50021, Potentially Explosive Atmospheres,

Protection n"

C-Tick

2

Australian Radiocommunications

Act,compliant with AS/NZS 2064, Industrial

Emissions

User Manual

Publication 1771ĆUM030

1 Use this conductor category information for planning conductor routing . Refer to publication 1770Ć4.1, Industrial

Automation Wiring and Grounding Guidelines."

2 See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other

certification details