Analog Output Module
7
Publication 1771-IN044C-EN-P - October 2002
To set the last state configuration jumpers,
proceed as follows.
!
ATTENTION
Do not insert modules
into or remove modules
from the I/O chassis
while system power is
ON. Failure to observe
this rule could result in
damage to module
circuitry and unexpected
machine operation.
Output
Range
Selection
Minimum
Value
Middle
Value
Maximum
Value
4Ć20mA
4mA
12mA
20mA
0Ć50mA
0mA
25mA
50mA
1Ć5V
1V
3V
5V
0Ć10V
0V
5V
10V
+10V
Ć10V
0V
+10V
These output conditions are active only if
the following conditions exist:
•
the module faults
•
the processor is in the PROGRAM or
TEST mode
•
rack switch 1 is in the reset position
Locate the last state configuration jumpers. You do not need to
remove the module cover.
11
Last State Output Level
Configuration Jumpers
MIN
MID
MAX
Front of Circuit Board
HOLD LAST STATE
Top View
13
Carefully reposition the jumper to reflect the desired values in
the table to the left.
12
Carefully pull up on the jumper to remove it from the pins.