Analog Output Module

7

Publication 1771-IN044C-EN-P - October 2002

To set the last state configuration jumpers,
proceed as follows.

!

ATTENTION

Do not insert modules

into or remove modules

from the I/O chassis

while system power is

ON. Failure to observe

this rule could result in

damage to module

circuitry and unexpected

machine operation.

Output

Range

Selection

Minimum

Value

Middle

Value

Maximum

Value

4Ć20mA

4mA

12mA

20mA

0Ć50mA

0mA

25mA

50mA

1Ć5V

1V

3V

5V

0Ć10V

0V

5V

10V

+10V

Ć10V

0V

+10V

These output conditions are active only if
the following conditions exist:

the module faults

the processor is in the PROGRAM or
TEST mode

rack switch 1 is in the reset position

Locate the last state configuration jumpers. You do not need to

remove the module cover.

11

Last State Output Level

Configuration Jumpers

MIN

MID

MAX

Front of Circuit Board

HOLD LAST STATE

Top View

13

Carefully reposition the jumper to reflect the desired values in

the table to the left.

12

Carefully pull up on the jumper to remove it from the pins.